Skip to main content

Metasys N2

The n2 adapter is a Johnson Controls Metasys N2 trunk adapter. N2 is a single-master bus, which shapes how you use this adapter.

Modes​

  • sniffer (default) — read-only. Decodes N2 traffic while the existing JCI supervisor (NAE/NCM) drives the trunk. This is the safe mode for a live system: OmniBus only listens.
  • master — actively polls configured devices. Use this only when no other N2 supervisor is on the wire — putting a second master on a single-master bus will disrupt it.

Decoding​

Frame decode and point decode are validated against captured frames.

Not yet validated against a live trunk

Decode coverage is verified against captured frames, not yet against a live NAE/NCM trunk. Validate against your system before relying on it.

Outputs​

OutputBehavior
MQTTPublishes decoded N2 points under the port prefix.
RESTStatus / control actions.
WebhooksFan out decoded points.

N2 points decoded by OmniBus can also be surfaced as BACnet objects (with configurable engineering units) when paired with the BACnet adapter — see BACnet MS/TP.